Parameter
Description
Configuration Principle
temperature and
humidity set points
correspond to the
selected control type
can be set.
Supply-air
: For a cold aisle, select
Supply-air
to control the temperature and
humidity around the air supply vent of the
precision air conditioner.
Cold-aisle
: For a cold aisle, select
Cold-aisle
to control the temperature and
humidity of the aisle. The temperature and
humidity values come from the humidity
and temperature sensor in the aisle.
Hot-aisle
: For a hot aisle, choose
Hot-aisle
to control the temperature and
humidity of the aisle. The temperature and
humidity values come from the humidity
and temperature sensor in the aisle.
Temp control
mode
Controls the
temperature inside the
room or aisles based
on the
Average
,
Maximum
, or
Minimum
of the
temperatures collected
by each sensor.
Average
: Select
Average
if the
temperature is to be controlled based on
the averaged data value collected by the
collector.
Maximum
: Select
Maximum
if the
temperature is to be controlled based on
the maximum data value collected by the
collector.
Minimum
: Select
Minimum
if the
temperature is to be controlled based on
the minimum data value collected by the
collector.
Supply-air temp
set point,
Supply-air humid
set point
Sets the required
humidity and
temperature in a room
or aisle.
The ACC controls the temperature and
humidity based on the set value. For example,
if
Temp control type
is set to
Supply-air
,
Supply-air temp set point
is set to
23.0
, and
Supply-air humid set point
is set to
50.0
, the
ACC will control the temperature and
humidity around the supply-air vent of the
precision air conditioner to a temperature of
23°C and humidity of 50% RH.
Return-air temp
set point,
Return-air humid
set point
Cold-aisle temp
set point,
Cold-aisle humid
set point
Hot-aisle temp
set point,
Hot-aisle humid
set point
Cold aisle sensor
1, 2, 3
Sets the sensors in
cold aisles to
Enable
.
Enable the corresponding humidity and
temperature sensor installed in the cold aisle.
Hot aisle sensor
1, 2, 3
Sets the sensors in hot
aisles to
Enable
.
Enable the corresponding humidity and
temperature sensor installed in the hot aisle.