Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
74
Menu
Parameter
Description
Default Value
value.
4.0°C
NetCol5000-A035
(025): 5.0°C
Max ret/sup air
temp diff
Indicates the parameter related
to the speed adjustment logic
of the indoor fan. You are not
recommended to change the
value.
NetCol5000-C:
10.0°C
NetCol5000-A035
(025),
NetCol5000-A020
: 12.0°C
Fan stop supply
air temp
Sets the supply air temperature
for shutting down the indoor
fan after the compressor,
electric heater, and humidifier
are shut down.
30.0°C
Dehum anti-cond
speed rise temp
diff
When the temperature
difference between the supply
air temperature and dew-point
temperature is less than
Dehum anti-cond speed rise
temp diff
during the
dehumidification, indoor fan
speed rises to prevent
condensation.
–5.0°C
Dehum anti-cond
speed fall lim
temp diff
When the temperature
difference between the supply
air temperature and dew-point
temperature is less than
Dehum anti-cond speed fall
lim temp diff
during the
dehumidification, indoor fan
speed fall is limited.
–2.0°C
Cool anti-cond
speed rise temp
diff
When the temperature
difference between the supply
air temperature and dew-point
temperature is less than
Cool
anti-cond speed rise temp
diff
during the cooling, indoor
fan speed rises to prevent
condensation.
–3.0°C
Cool anti-cond
speed fall lim
temp diff
When the temperature
difference between the supply
air temperature and dew-point
temperature is less than
Cool
anti-cond speed fall lim temp
diff
during the cooling, indoor
fan speed fall is limited.
0.0°C
Stop delay
Sets the delay time for shutting
down the indoor fan when the
30s