Advanced Cooling Controller
User Manual
5 FAQ
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
49
5.5 How to Troubleshoot the Fault When the System Is in
Upgrade Mode
Context
The system will display the following information and enter upgrade mode when the model
cannot be identified or does not match, or the software versions of the display board and
control board are incompatible.
The model cannot be identified. Entering upgrade mode...
The model does not match. Entering upgrade mode...
Failed to obtain the version information. Entering upgrade mode...
The display board and control board software versions are incompatible. Entering
the upgrade mode...
In the upgrade mode, you can only query the system version information. In this case,
perform the following steps for troubleshooting:
Upgrade mode is not supported in the following three circumstances:
The unit model is NetCol5000-A, and the monitoring version is V100R001C00B255.
The unit model is NetCol5000-A, and the monitoring version is V100R001C00B256.
The unit model is NetCol5000-C, and the monitoring version is V100R001C01B121.
Procedure
Step 1
After you have entered the home screen, choose
Maint
>
USB Operations
>
Software
Upgrade
, and check whether you can perform the upgrade.
If yes, upgrade the system version by referring to the software upgrade guide.
If no, proceed to
by following instructions of system prompts.
Step 2
If
The e-label board is not connected or the e-label is incorrect. Please connect or replace
the e-label board.
is displayed, power off the system, reconnect or replace the E-label board,
and then power on the system.
Step 3
If the fault persists, contact Huawei technical support.
----End
5.6 How to Fast Shut Down an Air Conditioner
Procedure
Step 1
On the home screen of the ACC, tap
Shutdown
.
The compressor stops running and the fan is shut down after the time delay.
Step 2
Disconnect the main power supply from the precision air conditioner.