Specifications
Environmental specifications
Table 1: Standard specifications
Specification
Value
—
Operating
0°C to 55°C (32°F to 131°F)
Nonoperating
-30°C to 60°C (-22°F to 140°F)
Relative humidity (noncondensing)
—
Operating
8% to 90% at 28°C (82.4°F) maximum wet bulb temperature
Non-Operating
5% to 95% at 38.7°C (101.7°F) maximum wet bulb
temperature
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 304.8 m (1.8°F per 1,000 ft) to 3,048 m (10,000 ft) is
applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). No restrictions on product configurations.
Not rated for operation over 3,048 m (10,000 ft).
Fan failure might reduce performance.
Table 2: ASHRAE Class A4 specifications
Specification
Value
—
Operating
0°C to 45°C (32°F to 113°F)
10°C to 35°C (50°F to 95°F) when GPU is installed
Nonoperating
-10°C to 60°C (-22°F to 140°F)
Relative humidity (noncondensing)
—
Operating
8% to 90% at 28°C (82.4°F) maximum wet bulb temperature
Non-Operating
5% to 95% at 38.7°C (101.7°F) maximum wet bulb
temperature
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 125 m (1.8°F per 410 ft) to 900 m (2,953 ft) is applicable.
No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). No restrictions on product configurations except for
rotating hard drives. PCI cards must be rated for continuous operation with 60°C cooling air. Not rated for operation over 3,048 m (10,000
ft).
Fan failure might reduce performance.
Specifications
173
Содержание ProLiant e910
Страница 148: ...148 Customer self repair...
Страница 149: ...Customer self repair 149...
Страница 150: ...150 Customer self repair...
Страница 158: ...c Remove the PCIe riser board Right PCIe riser board Left PCIe riser board 158 Removal and replacement procedures...
Страница 182: ...UID unit identification UEFI Unified Extensible Firmware Interface 182 Acronyms and abbreviations...