Description
Chassis
Fan configuration
Number of drives
supported by the
server
Maximum inlet
ambient
temperature
(12 LFF
backplane)
0 to 2 drives
30°C (86°F)
Apollo
DX2600
Gen10
Chassis
(24 SFF or 16
SFF + 8
NVMe
backplane)
Redundant and
nonredundant
0 to 6 drives
28°C (82.4°F)
Apollo
DX2800
Gen10
Chassis
(24 SFF
backplane
with SAS
expander)
Redundant and
nonredundant
0 to 24 drives
28°C (82.4°F)
Apollo
DX2800
Gen10
Chassis
(16 NVMe
backplane)
Redundant and
nonredundant
0 to 4 drives
30°C (86°F)
The drive capacity must be less than 10 TB.
The drive capacity must be greater than or equal to 10 TB.
If the component is installed in server 1 or server 2, and the server is installed in the Apollo DX2200 Gen10 Chassis,
drive blanks must be installed in drive bays 1-2 and 2-2. Similarly, if the component is installed in server 3 or server 4,
and the server is installed in the Apollo DX2200 Gen10 Chassis, drive blanks must be installed in drive bays 3-2 and
4-2.
DIMMs
In nonredundant fan mode, the 32 GB RDIMM, 64 GB LRDIMM, and 128 GB LRDIMM can support the
maximum inlet ambient temperature of 35°C (95°F).
Description
Chassis
Fan configuration
Number of drives
supported by the
server
Maximum inlet
ambient temperature
32 GB RDIMM Apollo
DX2200
Gen10
Chassis
Redundant
30°C (86°F)
30°C (86°F)
Table Continued
Specifications
117