34
HP StorageWorks XP12000 Disk Array Site Preparation Guide
2. In the floor clearance diagram:
• Clearance “A” is the space between the service clearance at the left
side of the array (10 cm for the kickplate) and any other object,
such as a desk or wall.
• Clearance “B” is the space between the service clearance at the
right side of the array (10 cm for the kickplate) and any other
object.
• Clearance “C” is the space between the service clearance at the
front of the array and any other object.
You use the value of C and your floor load rating to determine the
values for A and B.
3. Determine how much space you can assign to clearance C. For
maintenance purposes, try to make C larger (100 cm) rather than smaller
(0 cm). The smaller C is, the larger A and B must be.
4. In the table after the diagram, find the column for C. If your C value is
in between two table values, use the larger table value. Then, find the
row for your floor load rating. Where the column and row intersect is
the A+B value.
5. To determine clearance A and clearance B, divide the A+B value
between A and B. They do not need to be equal. For example, if the
A+B value from the table is 60 cm, then A can be 40 cm and B can be
20, or both A and B can be 30. However, if your configuration includes
only a DKC, or a DKC and one DKU, then A must be at least 28 cm
(11.1 in) to allow for opening the DKC front door.
Содержание StorageWorks XP12000
Страница 6: ...6 HP StorageWorks XP12000 Disk Array Site Preparation Guide ...
Страница 10: ...10 HP StorageWorks XP12000 Disk Array Site Preparation Guide ...
Страница 30: ...30 HP StorageWorks XP12000 Disk Array Site Preparation Guide DKC floor cutouts Figure 2 DKC floor cutouts ...
Страница 31: ...Site Requirements 31 DKU floor cutout Figure 3 DKU floor cutout ...