72
HP StorageWorks XP12000 Disk Array Site Preparation Guide
30-amp, single-phase DKU
30-amp, three-phase DKU
Table 27. 30-amp, 50 or 60 Hz, single-phase DKU operation
Nominal rated voltage (Vac)
Parameter
200
208
1
1 60 Hz only.
220
230
240
Minimum operating voltage (Vac)
184
191
202
212
221
Maximum operating voltage (Vac)
212
220
233
244
254
Rated line current per power cord (Arms)
9
8.7
8.2
7.8
7.5
Number of power cords
4
4
4
4
4
Recommended circuit breakers
30A
30A
30A
30A
30A
Number of circuit breakers
2
2 Units with only two power cords require only two circuit breakers.
4
4
4
4
4
Dropout carry-through time at minimum line voltage (ms)
60
60
60
60
60
Table 28. 30-amp, 50 or 60 Hz, three-phase DKU operation
Nominal rated voltage (Vac)
Parameter
200 208
1
1 60 Hz only.
220
230
240
380
400
415
Minimum operating voltage (Vac)
184
191
202
212
221
350
368
382
Maximum operating voltage (Vac)
212
220
233
244
254
403
424
440
Rated line current per power cord (Arms)
10.4 10.0
9.4
9.0
8.7
5.5
5.2
5.0
Number of power cords
2
2
2
2
2
2
2
2
Recommended circuit breakers
30A 30A 30A 30A 30A 30A 30A 30A
Number of circuit breakers
2
2
2
2
2
2
2
2
Dropout carry-through time at minimum line
voltage (ms)
60
60
60
60
60
60
60
60
Содержание StorageWorks XP12000
Страница 6: ...6 HP StorageWorks XP12000 Disk Array Site Preparation Guide ...
Страница 10: ...10 HP StorageWorks XP12000 Disk Array Site Preparation Guide ...
Страница 30: ...30 HP StorageWorks XP12000 Disk Array Site Preparation Guide DKC floor cutouts Figure 2 DKC floor cutouts ...
Страница 31: ...Site Requirements 31 DKU floor cutout Figure 3 DKU floor cutout ...