Site Requirements
39
Table 9. A+B based on C and floor load rating — DKC and one DKU
Floor load
rating
(kg/m2)
C=0,
A+B must =
C=20 cm (7.9 in),
A+B must =
C=40 cm (15.8 in),
A+B must =
C=60 cm (23.6 in),
A+B must =
C=100 cm (39.4 in),
A+B must =
500
80
60
40
20
0
450
110
90
70
50
20
400
160
130
100
80
50
350
230
190
160
130
90
300
330
280
240
210
160