Electrical Specifications
71
30-amp, three-phase DKC
50-amp, single-phase DKU
Table 25. 30-amp, 50 or 60 Hz, three-phase DKC operation
Nominal rated voltage (Vac)
Parameter
200 208
1
1 60 Hz only.
220
230
240
380
400
415
Minimum operating voltage (Vac)
184
191
202
212
221
350
368
382
Maximum operating voltage (Vac)
212
220
233
244
254
403
424
440
Rated line current per power cord (Arms)
13 12.5 11.9 11.3 10.9
6.9
6.5
6.3
Number of power cords
2
2
2
2
2
2
2
2
Recommended circuit breakers
30A 30A 30A 30A 30A 30A 30A 30A
Number of circuit breakers
2
2
2
2
2
2
2
2
Dropout carry-through time at minimum line
voltage (ms)
60
60
60
60
60
60
60
60
Table 26. 50-amp, 50 or 60 Hz, single-phase DKU operation
Nominal rated voltage (Vac)
Parameter
200
208
1
1 60 Hz only.
220
230
240
Minimum operating voltage (Vac)
184
191
202
212
221
Maximum operating voltage (Vac)
212
220
233
244
254
Rated line current per power cord (Arms)
18
17.3
16.4
15.7
15.0
Number of power cords
2
2
2
2
2
Recommended circuit breakers
50A
50A
50A
50A
50A
Number of circuit breakers
2
2
2
2
2
Dropout carry-through time at minimum line voltage (ms)
60
60
60
60
60
Содержание StorageWorks XP12000
Страница 6: ...6 HP StorageWorks XP12000 Disk Array Site Preparation Guide ...
Страница 10: ...10 HP StorageWorks XP12000 Disk Array Site Preparation Guide ...
Страница 30: ...30 HP StorageWorks XP12000 Disk Array Site Preparation Guide DKC floor cutouts Figure 2 DKC floor cutouts ...
Страница 31: ...Site Requirements 31 DKU floor cutout Figure 3 DKU floor cutout ...