HP ProLiant server errors 64
CAUTION:
Only authorized technicians trained by HP should attempt to remove the system
board. If you believe the system board requires replacement, contact HP Technical Support ("
HP
contact information
" on page
399
) before proceeding.
2.
Run Insight Diagnostics and replace failed components as indicated.
305- Redundant ROM Error: Both the Primary and Backup System ROMs are invalid
Action:
Flash the Primary and Backup System ROMs to the desired revisions. If the server fails to boot,
perform the flash update via iLO.
306- Redundant ROM Error: iLO FW did not set the Primary System ROM
...The error has been corrected. iLO FW may have an issue.
Action:
Remove power. If issue persists, update iLO FW. If the issue persists, contact HP service.
307- Fan Failure Detected - Fan X Failed
308- Required Fan NOT Installed – Fan X Missing
Action:
Install the indicated fan.
309- Insufficient Fan Solution
...The system does not have the minimum required number of operating fans.
Action:
Install the minimum required fans to prevent possible damage to system components.
310- IMPORTANT: Fan Solution Not Redundant
...The system does not have the minimum required operating fans for redundancy.
Action:
Install additional fans if redundancy is required.
311- HP Smart Storage Battery Configuration Error
...The system has exceeded the installed battery capacity.
Action:
Increase battery capacity or remove battery-backed devices. For more information, see the user
guide.
312- HP Smart Storage Battery X Failure
...Communication with the battery failed and its output may not be enabled.
Action:
Verify the battery is properly installed. For more information, see the user guide. If the issue persists,
contact HP support.
313- HP Smart Storage Battery X Failure
...Battery Shutdown Event Code: XXXX
Action:
Restart the system. If the issue persists, contact HP support.
314- A critical error occurred prior to this system boot
Action:
Check the Integrated Management Log (IML) for possible additional information.