Chapter 7
Removing and Replacing Components
Hot-Swap Power Supplies
204
Hot-Swap Power Supplies
The HP Integrity rx4640 Server has two 200-240 VAC hot-swap power supply units (PSU). These PSUs are located at the rear
of the HP server. The supported configuration of the HP Integrity rx4640 Server requires a minimum of one PSU be installed.
CAUTION
Observe all ESD safety precautions before attempting this procedure. Failure to follow ESD safety
precautions could result in damage to the server.
NOTE
A hot-swap device does not require interaction with the operating system before the device is removed from
or installed into the server.
The AC power to the server does not have to be off to remove or replace a hot-swap power supply.
Power Supply Load Order
The supported configuration of your hp Integrity rx4640 Server requires a minimum of one 200-240 VAC PSU. A second,
optional hot-swap PSU, may be installed to provide N+1 capability. Each hot-swap requires a separate power cord.
The left side (viewing from the rear) hot-swap PSU is identified as P 0, the second hot-swap power supply is identified as P 1.
Each hot-swap PSU requires a separate power cord be installed in the appropriate power cord receptacle and attached to a
power cord support bracket.
CAUTION
The empty hot-swap PSU slot P 1 must remain closed with the supplied metal cover when a second PSU is
not used. Your server may be damaged due to overheating if the cover does not remain in place.
WARNING
Be careful when installing a hot-swap power supply. It is heavier than it appears.
CAUTION
If the system is powered down, install the hot-swap PSU into the server before attaching the new power cord
at the rear of the system. Failure to observe this caution will result in damage to the server.
Removing a Hot-Swap Power Supply
To remove a hot-swap PSU, perform the following steps:
CAUTION
Be careful when removing the hot-swap power supply. It is heavier than it appears.
Step 1.
If rack mounted, slide the HP Server back out of the rack until it stops. See “Accessing a Rack Mounted Server” on
page 141.
Step 2.
Remove the power cord plug from the power receptacle.
Step 3.
Loosen the captive thumbscrew located at the top left of the PSU.
Step 4.
Grasp the handle and pull the PSU out of the server.
Содержание Integrity rx4640
Страница 8: ...Contents 8 ...
Страница 14: ...Chapter 1 About This Document Where to Get Help 14 ...
Страница 28: ...Chapter 2 Controls Ports and Indicators Rear Panel 28 ...
Страница 86: ...Chapter 4 Installing Additional Components and Configuring Booting the Server 86 ...
Страница 120: ...Chapter 5 Utilities Management Processor Command Interface 120 ...
Страница 121: ...Chapter 5 Utilities Management Processor Command Interface 121 ...
Страница 122: ...Chapter 5 Utilities Management Processor Command Interface 122 ...
Страница 138: ...Chapter 6 Troubleshooting Troubleshooting Using Offline Support Tools 138 ...
Страница 139: ...Chapter 6 Troubleshooting Troubleshooting Using Offline Support Tools 139 ...
Страница 140: ...Chapter 6 Troubleshooting Troubleshooting Using Offline Support Tools 140 ...
Страница 190: ...Chapter 7 Removing and Replacing Components OLX Dividers 190 Figure 7 25 OLX Divider Latch CLOSED OPEN ...
Страница 197: ...Chapter 7 Removing and Replacing Components Hot Plug Disk Drives 197 Figure 7 29 Volume Filler Installation in Slot 2 ...
Страница 210: ...Chapter 7 Removing and Replacing Components DVD Drive 210 Step 3 Replace the front bezel ...
Страница 216: ...Chapter 7 Removing and Replacing Components Display Board 216 Figure 7 36 Display Board Removal and Replacement ...
Страница 221: ...Chapter 7 Removing and Replacing Components QuickFind Diagnostic Board 221 ...
Страница 222: ...Chapter 7 Removing and Replacing Components QuickFind Diagnostic Board 222 ...
Страница 226: ...Chapter 8 Parts Information Field Replaceable Parts FRU List 226 ...
Страница 229: ...Chapter 9 Specifications Dimensions and Weights 229 ...
Страница 230: ...Chapter 9 Specifications Dimensions and Weights 230 ...