DC SAN Backbone Director hardware reference guide
73
Figure 30
Control processor blade (CP8)
Replacing a control processor blade (CP8)
To replace a CP blade (slot 6 or 7):
CAUTION:
Wear a grounded ESD strap when handling a CP8 blade. Use the grounding connections
above the power connectors on the chassis.
1.
Open the ejector handles to approximately 45 degrees. Orient the CP blade so that the handles are
toward you and the flat metal side is on your left.
2.
Align the flat metal side of the CP blade inside the lower and upper blade guides in the slot. Slide the
CP blade into the slot until it is firmly seated, see
Figure 30
).
3.
Tighten the thumb screw inside each handle using the Phillips screwdriver.
4.
Turn the CP blade on by sliding the ON/OFF switch in the top handle up, to cover the thumb screw.
5.
Verify that the power LED is green. If not, ensure that the CP blade has power and is firmly seated and
that the ejectors are in the locked position.
6.
Connect the cables to the new CP blade.
7.
Verify the installation. See ”
Verifying operation of the new CP blade
” on page 73.
8.
Replace the chassis door. See ”
Cable management comb
” on page 65.
Verifying operation of the new CP blade
To verify that boot and POST are complete on the new CP blade and that the CP blade has achieved
failover redundancy:
1.
Log into the active CP as admin.
2.
Enable the redundancy feature using the
haEnable
command.
3.
Verify HA is enabled using the
haShow
command. The command output includes
HA Enabled
Heartbeat Up
and
HA-state in sync
.
26385a
Содержание A7990A - StorageWorks SAN Director 4/16 Blade Switch
Страница 8: ...8 ...
Страница 27: ...DC SAN Backbone Director hardware reference guide 27 I Figure 3 14U Rack Mount Kit contents 26419a ...
Страница 62: ...62 Monitor system components ...
Страница 100: ...100 Installing Field replaceable units FRUs ...
Страница 122: ...122 Intelligent blades ...
Страница 132: ...132 Regulatory compliance and safety notices ...
Страница 134: ...134 Port numbering templates 26390a ...
Страница 135: ...DC SAN Backbone Director hardware reference guide 135 26389a ...
Страница 136: ...136 Port numbering templates 26388a ...
Страница 137: ...DC SAN Backbone Director hardware reference guide 137 FC 10 6 0 2 3 4 5 1 2 3 4 5 FC 10 6 2 3 4 5 1 1 0 0 26391a ...
Страница 140: ...140 Port numbering templates ...