284
22 Design for injection system
Instead of a diverting system, an injection system can also
be installed in the load circuit.
Note
The injection system is particularly well suited for
applications where only a low heat output is required
due to high internal heat gains.
Please note the following:
■
In the design for the injection system, the pumps in the
load circuit are also controlled directly by the DigiUnit
terminal box, as well as the mixing valves.
■
Terminals for wiring the mixing valves are located in the
connection box.
■
Terminals for wiring the pumps in the load circuit are
located in the DigiUnit terminal box.
■
Make sure that valves and pumps which meet the
following requirements are provided on-site.
Requirements for mixing valves
■
Use three-way mixing valves with linear characteristics
and high quality.
■
The valve authority must be ≥ 0.3.
■
The maximum run time of the valve actuator is 150 s.
■
The valve actuator must be continuous, i.e. the stroke
changes in proportion to the control voltage (DC 0…10 V).
■
The valve actuator must be designed for emergency
operation with a separate manual control (AC 24 V).
Requirements for pumps
Voltage _______ 3 x 400 V
Output _______ up to 1.8 kW
Current _______ up to 5.0 A
Heating pump
Mixing valve heating
Cooling pump
Mixing valve cooling
Table K28: Electrical connections
Options
Design for injection system
Содержание RoofVent CON-9
Страница 2: ......
Страница 4: ...2...
Страница 6: ...4...
Страница 8: ...6...
Страница 12: ...10 RoofVent LHW Use...
Страница 40: ...38 RoofVent LKW Use...
Страница 68: ...66 RoofVent twin heat Use...
Страница 94: ...92 RoofVent twin cool Use...
Страница 122: ...120 RoofVent twin pump Use...
Страница 150: ...148...
Страница 154: ...152 RoofVent condens Use...
Страница 180: ...210 RoofVent LH Construction and operation...
Страница 208: ...238 RoofVent LK Use...
Страница 256: ...286...
Страница 268: ...298...
Страница 274: ...304...
Страница 279: ......