158
3.3 Air flow rate, electrical connections
Unit type
CON-9
Air distribution
Nominal air flow rate
1) 2)
Supply air m³/h
8000
Exhaust air m³/h
8000
Floor area reached
Max.
m²
797
Energy recovery
Heat recovery efficiency, dry
%
63
Heat recovery efficiency, wet
%
73
Fan characteristics
Supply voltage
V AC
3 x 400
Permitted voltage tolerance
%
± 10
Frequency
Hz
50
Active power per motor
kW
3.0
Current consumption
A
6.5
Set point of thermal relays
A
7.5
Speed of rotation (nominal)
rpm
1435
Actuators
Supply voltage
V AC
24
Frequency
Hz
50
Control voltage
V DC
2…10
Torque
Nm
10
Run time for 90° rotation
s
150
Filter monitoring
Factory setting of differential pressure switch
Pa
300
Gas condensing boiler
Nominal heat output at 40/30 °C
kW
12.8 – 60.7
Nominal heat load
kW
12.2 – 57.3
Standard efficiency
%
109.0 / 98.2
Gas consumption for 0 °C / 1013 mbar
Natural gas E W
o
= 15.0 kWh/m³
H
u
= 9.97 kWh/m³
m³/h
5.8
Natural gas
LL
W
o
= 12.4 kWh/m³
H
u
= 8.57 kWh/m³
m³/h
6.7
Gas pressure, natural gas E/LL
mbar
18 – 50
Gas connection (male thread)
"
R ¾
Condensate
l/h
5.4
1)
Refers to: RoofVent
®
condens with vertical supply air discharge direction
2)
In automatic mixed air operation where fresh air temperatures are low:
– Supply air:
4000 m³/h fresh air, 4000 m³/h recirculation
– Exhaust air:
4000 m³/h
Table G4: Technical data, RoofVent
®
condens
RoofVent
®
condens
Technical data
Содержание RoofVent CON-9
Страница 2: ......
Страница 4: ...2...
Страница 6: ...4...
Страница 8: ...6...
Страница 12: ...10 RoofVent LHW Use...
Страница 40: ...38 RoofVent LKW Use...
Страница 68: ...66 RoofVent twin heat Use...
Страница 94: ...92 RoofVent twin cool Use...
Страница 122: ...120 RoofVent twin pump Use...
Страница 150: ...148...
Страница 154: ...152 RoofVent condens Use...
Страница 180: ...210 RoofVent LH Construction and operation...
Страница 208: ...238 RoofVent LK Use...
Страница 256: ...286...
Страница 268: ...298...
Страница 274: ...304...
Страница 279: ......