231
E
E
F
G
H
I
J
K
L
M
N
Component
Description
Voltage
Cable
Option Comment
DigiUnit
terminal box
Power supply
3 x 400 V
LH-6:
5 x 4 mm²
LH-9:
5 x 6 mm²
novaNet system bus
2 x 0.16 mm²
For bus cable specifications,
see Section L, chap. 2.4
Heating pump
3 x 400 V
4 x 2.5 mm²
For injection system
Zone control
panel
3-phase
Power supply
3 x 400 V
5 x … mm²
Depending on options
novaNet system bus
2 x 0.16 mm²
For bus cable specifications,
see Section L, chap. 2.4
Room air sensor
2 x 1.5 mm²
Max. 170 m
Shielded cable
Fresh air sensor
2 x 1.5 mm²
Max. 170 m
Enable heating
Volt-free
Max. 230 V
3 x 1.5 mm²
2 A max.
Per zone
Trouble input heating
24 V
3 x 1.5 mm²
Per zone
Collective trouble indicator
Volt-free
Max. 230 V
3 x 1.5 mm²
Max. 6 A
Special function on terminal
24 V
3 x 1.5 mm²
Per special function
Power supply for
RoofVent
®
LH
3 x 400 V
LH-6:
5 x 4 mm²
LH-9:
5 x 6 mm²
Per RoofVent
®
LH
Main pump
3 x 400 V
4 x 2.5 mm²
Per pump
Humidity sensor
24 V
4 x 1.5 mm²
Max. 170 m
CO
2
sensor
24 V
4 x 1.5 mm²
Max. 170 m
Variant:
Zone control
panel
1-phase
Power supply
1 x 230 V
3 x … mm²
Depending on options
novaNet system bus
2 x 0.16 mm²
For bus cable specifications,
see Section L, chap. 2.4
Room air sensor
2 x 1.5 mm²
Max. 170 m
Shielded cable
Fresh air sensor
2 x 1.5 mm²
Max. 170 m
Enable heating
Volt-free
Max. 230 V
3 x 1.5 mm²
2 A max.
Per zone
Trouble input heating
24 V
3 x 1.5 mm²
Per zone
Collective trouble indicator
Volt-free
Max. 230 V
3 x 1.5 mm²
Max. 6 A
Special function on terminal
24 V
3 x 1.5 mm²
Per special function
Main pump
1 x 230 V
3 x 1.5 mm²
Per pump
Humidity sensor
24 V
4 x 1.5 mm²
Max. 170 m
CO
2
sensor
24 V
4 x 1.5 mm²
Max. 170 m
Table I13: Cable list
RoofVent
®
LH
Transport and installation
Содержание RoofVent CON-9
Страница 2: ......
Страница 4: ...2...
Страница 6: ...4...
Страница 8: ...6...
Страница 12: ...10 RoofVent LHW Use...
Страница 40: ...38 RoofVent LKW Use...
Страница 68: ...66 RoofVent twin heat Use...
Страница 94: ...92 RoofVent twin cool Use...
Страница 122: ...120 RoofVent twin pump Use...
Страница 150: ...148...
Страница 154: ...152 RoofVent condens Use...
Страница 180: ...210 RoofVent LH Construction and operation...
Страница 208: ...238 RoofVent LK Use...
Страница 256: ...286...
Страница 268: ...298...
Страница 274: ...304...
Страница 279: ......