3.6 Minimum and maximum distances
X/2
X
Y
Unit type
CON-9
Align the RoofVent
®
units so that no unit draws in the
exhaust air from another unit as fresh air.
The extract air grille must be easily accessible.
Provide a clear space of approx. 1.5 m on the side
opposite to the coil connections for service and main-
tenance.
The stream of supply air must be able to spread unob-
structed (note position of beams and lamps).
Unit clearance X
Min.
m
13.0
Max.
m
28.0
Mounting height Y
1)
Min.
1)
m
5.0
Max.
2)
m 14.0 … 16.0
1)
The minimum height can be reduced by 1 m in each case using the 'Air
outlet box' option (see Section K 'Options').
2)
The maximum height varies depending on the ancillary conditions (for
values, see Table G6).
Table G7: Minimum and maximum distances
RoofVent
®
condens
Technical data