
16
3.3 Air flow rate, electrical connections
Unit type
LHW-6
LHW-9
LHW-10
Air distribution
Nominal air flow rate
1)
Supply air m³/h
5500
8000
8800
Exhaust air m³/h
5500
8000
8800
Floor area reached
Max.
m²
480
797
915
Energy recovery
Heat recovery efficiency, dry
%
60
63
57
Heat recovery efficiency, wet
%
68
73
65
Fan characteristics
Supply voltage
V AC
3 x 400
3 x 400
3 x 400
Permitted voltage tolerance
%
± 10
± 10
± 10
Frequency
Hz
50
50
50
Active power per motor
kW
1.8
3.0
4.5
Current consumption
A
4.0
6.5
9.9
Set point of thermal relays
A
4.6
7.5
11.4
Speed of rotation (nominal)
rpm
1440
1435
1450
Actuators
Supply voltage
V AC
24
24
24
Frequency
Hz
50
50
50
Control voltage
V DC
2…10
2…10
2…10
Torque
Nm
10
10
10
Run time for 90° rotation
s
150
150
150
Filter monitoring
Factory setting of differential pressure switch
Pa
300
300
300
1)
Refers to: RoofVent
®
LHW with heating coil type B and vertical supply air discharge direction
Table B4: Technical data, RoofVent
®
LHW
RoofVent
®
LHW
Technical data
Содержание RoofVent CON-9
Страница 2: ......
Страница 4: ...2...
Страница 6: ...4...
Страница 8: ...6...
Страница 12: ...10 RoofVent LHW Use...
Страница 40: ...38 RoofVent LKW Use...
Страница 68: ...66 RoofVent twin heat Use...
Страница 94: ...92 RoofVent twin cool Use...
Страница 122: ...120 RoofVent twin pump Use...
Страница 150: ...148...
Страница 154: ...152 RoofVent condens Use...
Страница 180: ...210 RoofVent LH Construction and operation...
Страница 208: ...238 RoofVent LK Use...
Страница 256: ...286...
Страница 268: ...298...
Страница 274: ...304...
Страница 279: ......