302
4 Condensation lilmit
RoofVent
®
twin heat / twin cool / twin pump
At high humidity levels or extremely low fresh air tempera-
tures, humidity in the extract air may condense in plate heat
exchanger 2. Diagram M1 shows under what air conditions
condensation occurs. In applications where the condensation
limit is exceeded:
■
Connect the condensate drain connection in the combi
box to a condensate drainage system.
■
Where required, use a condensate pump to discharge
condensate through waste water pipes directly below the
ceiling or onto the roof.
■
Use the option drop eliminator for the plate heat
exchanger 1 in the roof unit.
Extract air temperature
Relative extract air humidity [%]
20
30
40
50
60
70
80
90
-20
-15
-10
-5
0
5
10
20 °C
22 °C
24 °C
26 °C
28 °C
Fresh air temperature [°C]
Refers to: Air pressure 1013 hPa
Diagram 1: Condensation limit for plate heat exchanger 2 in RoofVent
®
twin units
System design
Condensation lilmit
Содержание RoofVent CON-9
Страница 2: ......
Страница 4: ...2...
Страница 6: ...4...
Страница 8: ...6...
Страница 12: ...10 RoofVent LHW Use...
Страница 40: ...38 RoofVent LKW Use...
Страница 68: ...66 RoofVent twin heat Use...
Страница 94: ...92 RoofVent twin cool Use...
Страница 122: ...120 RoofVent twin pump Use...
Страница 150: ...148...
Страница 154: ...152 RoofVent condens Use...
Страница 180: ...210 RoofVent LH Construction and operation...
Страница 208: ...238 RoofVent LK Use...
Страница 256: ...286...
Страница 268: ...298...
Страница 274: ...304...
Страница 279: ......