62
Heating and cooling in the 4-pipe system
There is an additional heating section installed in the below-
roof unit:
■
Heating section H.A / H.B / H.C
Aluzinc sheet steel casing, includes the LPHW heating coil
made of copper tubes and aluminium fins and the frost
controller.
Type
H.__-…
Heat output
…
kW
Heating medium LPHW
… / …
°C
At air inlet temperature
…
°C
Design for injection system ES
Control and high-voltage section for the heating/cooling
pump integrated into the DigiUnit terminal box
8.6 Control systems
Digital control system for the energy-optimised operation of
decentralised indoor climate systems:
■
System set up according to OSI reference model
■
Onsite connection to the individual control modules using
novaNet system bus in a serial topology
■
Cross-communication with equal priority (peer-to-peer/
multiplier) using novaNet log
■
Fast reaction times due to data transmission on an events
basis
■
Control modules pre-addressed in the factory with
integrated lightning protection and battery-buffered RAM
modules
■
No onsite engineering (binding) required
DigiNet operator terminals
DigiMaster DM5
Pre-programmed Plug-&-Play operator terminal with graphic
user interface, consisting of a touch panel with colour display,
installed in the door of the zone control panel.
■
Monitoring and setting the DigiNet system (operating
modes, temperature values, scheduler, calendar, alarm
handling, control parameters)
DigiCom DC5
Package consisting of operating software, novaNet router
and connection cables for using the Hoval DigiNet with a PC:
■
Monitoring and setting the DigiNet system (operating
modes, temperature values, scheduler, calendar, alarm
handling and forwarding, control parameters)
■
Trend function, data storage and logbook
■
Differentiated password protection
DigiEasy DE5
Additional unit for operating a control zone, for installation at
any location in a triple flush socket box or in the door of the
zone control panel:
■
Display of the current room temperature set value
■
Increase or decrease the set value by up to 5 °C
■
Display and acknowledge alarms
■
Switch the operating mode
Options
■
Window for DigiMaster
■
IP65 framework
■
novaNet socket
■
novaNet router
■
4 special functions with switch
■
8 special functions with 2 switches
■
Special function on terminal
■
DigiEasy installation
DigiNet zone control panel
The zone control panel (coated sheet steel, RAL 7035)
contains:
■
1 fresh air sensor
■
1 transformer 230/24 V
■
2 circuit breakers for transformer (1-pin)
■
1 relay
■
1 safety relay (2-pin, external)
■
Input and output terminals (top)
■
1 wiring diagram of the system
■
1 DigiZone controller, 1 heating/cooling selector switch,
1 relay and 1 room air sensor (supplied) for each control
zone
DigiZone controller DZ5
Control unit for each control zone, integrated in the zone
control panel:
■
Processes the inputs room and fresh air temperature, trouble
heating, trouble cooling and special functions (optional)
■
Controls the operating modes according to the scheduler
■
Sets the outputs for the enable heating, enable cooling
and the collective trouble indicator
Options
■
Alarm lamp
■
Socket
■
Control of the main pump
■
2-pin circuit breakers
■
Power supply for indoor climate units with integrated
DigiUnit controller
■
Integration of indoor climate units without integrated
DigiUnit controller
■
Room temperature average value
■
DigiPlus controller
■
Humidity sensor
■
CO
2
sensor
■
Base
RoofVent
®
LKW
Specification texts
Содержание RoofVent CON-9
Страница 2: ......
Страница 4: ...2...
Страница 6: ...4...
Страница 8: ...6...
Страница 12: ...10 RoofVent LHW Use...
Страница 40: ...38 RoofVent LKW Use...
Страница 68: ...66 RoofVent twin heat Use...
Страница 94: ...92 RoofVent twin cool Use...
Страница 122: ...120 RoofVent twin pump Use...
Страница 150: ...148...
Страница 154: ...152 RoofVent condens Use...
Страница 180: ...210 RoofVent LH Construction and operation...
Страница 208: ...238 RoofVent LK Use...
Страница 256: ...286...
Страница 268: ...298...
Страница 274: ...304...
Страница 279: ......