63
4 220 456 / 02
M
AINTENANCE
6.8
BIC 970 automatic function device parameter list
!
WARNING
Changes to the BIC may only be made by authorised Hoval customer service technicians. The following table is intended solely to provide information
for the Hoval customer service technician!
6.8.1 Automatic function device UltraGas
®
2
Parameters
CAN bus Description
Tree
Unit
Plant Setting values 51-UltraGas
®
2
(125) 51-UltraGas
®
2
(150) 51-UltraGas
®
2
(190) 51-UltraGas
®
2
(230) 51-UltraGas
®
2
(300) 51-UltraGas
®
2
(350) 51-UltraGas
®
2
(400) 51-UltraGas
®
2
(450) 51-UltraGas
®
2
(530) 51-UltraGas
®
2
(620) 51-UltraGas
®
2
(700) 51-UltraGas
®
2
(800) 51-UltraGas
®
2
(1000) 51-UltraGas
®
2
(1
100)
51-UltraGas
®
2
(1300) 51-UltraGas
®
2
(1550)
33287
SC1-6 debounce time
Configuration
s
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
33537
Valve testing system function
0 = OFF
1 = Valve testing system available
Vlv testing sys
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
33793
Function air level mntrg.
0 = Max. switch
1 = Min. and max. switches
2 = Pressure sensor
Air level mntrg.
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
34561
Y6 function main gas valve
0 = OFF
1 = External main gas valve
Gas valves
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
36889
Minimum speed fan
Primary air fan
rpm
1100 1200 1000 1000 1000 1100 1000 1000
900 900
1000
900
1100 1100 1000 1000
36890
Maximum speed fan
Primary air fan
rpm
4600 5500 4400 4800 5200 5300 5400 5400 4500 4500 4800 4600 5700 5800 5000 5000
36892
Fan speed pre-ventilation
Primary air fan
rpm
4600 5500 4400 4800 5200 5300 5400 5400 4500 4500 4800 4600 5700 5800 5000 5000
36898
Start speed
Primary air fan
rpm
1600
1900
1600 1600 1700 1700 1600 1600 1600 1600 1600 1600 1800 1800 1700 1700
36902
Speed post-ventilation normal
Primary air fan
rpm
1100 1200 1000 1000 1000 1100 1000 1000
900 900
1000
900
1100 1100 1000 1000
36913
Run time post-ventilation blocking
Primary air fan
s
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
36919
Run time post-ventilation locking
Primary air fan
s
180 180 180 180 180 180 180 180 180 180 180 180 180 180 180 180
37121
Number of Hall pulses
Primary air fan
3
3
3
3
3
3
3
3
3
3
3
3
4
4
5
5
36920
Rising ramp flushing
Primary air fan
rpm
500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
36921
Falling ramp flushing
Primary air fan
rpm
200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200
36922
Rising ramp normal operation
Primary air fan
rpm
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
36923
Falling ramp normal operation
Primary air fan
rpm
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
37383
Blocking temperature WF
Heat gen. sensor
°C
103 103 103 103 103 103 103 103 103 103 103 103 103 103 103 103
37384
Switching diff. from blocking temp. WF
Heat gen. sensor
K
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
37387
Main pump frost protection ON
Heat gen. sensor
°C
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
37388
Main pump frost protection OFF
Heat gen. sensor
°C
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
37389
Heat gen. frost protection ON
Heat gen. sensor
°C
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
37390
Heat gen. frost protection OFF
Heat gen. sensor
°C
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10