40
4 220 456 / 02
INSTAllATION
4.6.2.1 Example
Gas boiler with
-
calorifier
- 1 direct circuit and 1-... mixer circuit(s) (LT separation)
Hydraulic schematic BDHE050
1
A
B
D
E
C
F
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
A
B
D
E
C
F
BDHE050.dwg
Achtung !
Für die Installation muss das anlagenbezogene Schema verwendet werden!
Attention!
This is just a schematic. For installation please use the detail-plan!
Attenzione!
Per la messa in opera, utilizzare le schema dettagliato!
Attention!
Pour la réalisation pratique de l'installation, il faut utiliser le schéma détaillé!
Datum:
Datei:
Version:
Blatt:
Hydr.
Verbindungshinweise /
Notice / Nota / Remarque:
1
BDHE050
Name:
00
FEDI
17.08.2020
MK1
T
T
VF1
YK1
DKP
T
T
SLP
T
T
MK2
T
T
B1.2
VF2
YK2
AF
RBM
TTE-GW
TTE-WEZ
B1.1
HT
NT
P
T
P
P
max
STB
SF
T
TTE-FE
HK
UltraGas 2
1
A
B
D
E
C
F
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
A
B
D
E
C
F
BDHE050.dwg
Achtung !
Für die Installation muss das anlagenbezogene Schema verwendet werden!
Attention!
This is just a schematic. For installation please use the detail-plan!
Attenzione!
Per la messa in opera, utilizzare le schema dettagliato!
Attention!
Pour la réalisation pratique de l'installation, il faut utiliser le schéma détaillé!
Datum:
Datei:
Version:
Blatt:
Hydr.
Verbindungshinweise /
Notice / Nota / Remarque:
1
BDHE050
Name:
00
FEDI
17.08.2020
MK1
T
T
VF1
YK1
DKP
T
T
SLP
T
T
MK2
T
T
B1.2
VF2
YK2
AF
RBM
TTE-GW
TTE-WEZ
B1.1
HT
NT
P
T
P
P
max
STB
SF
T
TTE-FE
HK
UltraGas 2
Fig. 36
TTE-WEZ TopTronic
®
E basic module heat generator (installed)
VF1
Flow sensor 1
B1.1
Flow temperature monitor (if required)
MK1
Pump, mixer circuit 1
YK1
Actuator, mixer 1
AF
Outdoor sensor
SF
Calorifier sensor
DKP
Pump for heating circuit without mixer
SLP
Calorifier charging pump
Optional
RBM
TopTronic
®
E room control module
TTE-GW
TopTronic
®
E gateway
TTE-FE HK TopTronic
®
E module expansion heating circuit
VF2
Flow sensor 2
B1.2
Flow temperature monitor (if required)
MK2
Pump, mixer circuit 2
YK2
Actuator, mixer 2
NOTICE
Close unused connection nozzles tightly.
Important notices:
• The example schematics merely show the
basic principle and do not contain all informa-
tion required for installation. Installation must
be carried out according to the conditions on
site, dimensioning and local regulations.
•
With underfloor heating, a flow temperature
monitor must be installed.
•
Shut-off devices to the safety equipment
(pressure expansion tank, safety valve,
etc.) must be secured against unintentional
closing!
• Install sacks to prevent single-pipe gravity
circulation!
• An automatic air vent (AAV) must be in-
stalled before the shut-off valve. This is not
supplied by Hoval.