24
4 220 456 / 02
TECHNICAl INFORMATION
3.3.2 UltraGas
®
2 (300-450)
Type
(300)
(350)
(400)
(450)
• Nominal heat output at 80/60 °C, natural gas
kW
62-283
70-332
80-378
87-429
• Nominal heat output at 50/30 °C, natural gas
kW
67-302
73-350
85-401
96-453
• Nominal heat output at 80/60 °C, propane
2)
kW
-
-
-
-
• Nominal heat output at 50/30 °C, propane
2)
kW
-
-
-
-
• Nominal heat input with natural gas
1)
kW
62-291
70-338
78-385
89-437
• Nominal heat input with propane
2)
kW
-
-
-
-
•
Operating pressure heating min./max. (PMS)
bar
1/6
1/6
1/6
1/6
•
Max. operating temperature (T
max
)
°C
95
95
95
95
• Boiler water content (V
(H20)
)
l
522
496
483
457
• Flow resistance boiler
See diagram
•
Minimum circulation water quantity
l/h
-
-
-
-
• Boiler weight (without water capacity, incl. cladding)
kg
770
810
830
850
•
Boiler efficiency at 80/60 °C in full-load operation (NCV/GCV)
3)
%
98.2/88.5
98.1/88.5
98.3/88.6
98.3/88.7
•
Boiler efficiency at 30% partial load operation (EN 15502) (NCV/GCV)
3)
%
109.2/98.4
108.4/97.7
108.3/97.6
108.3/97.9
•
Room heating energy efficiency
- without control
ηs
%
93
93
93
-
- with control
ηs
%
95
95
95
-
- with control and room sensor
ηs
%
97
97
97
-
• NOx class (EN 15502)
6
6
6
6
• Nitrogen oxide emissions (EN 15502) (GCV)
NOx
mg/kWh
31
38
41
37
• Carbon monoxide emissions at 50/30 °C
4)
CO
mg/Nm
3
21
21
26
31
• O
2
content in flue gas min./max. output
5)
%
6.0/5.9
6.0/5.9
6.0/5.9
5.9/5.8
• CO
2
content in flue gas at min./max. output
%
8.5/8.6
8.6/8.6
8.5/8.6
8.6/8.6
• Heat loss in standby mode
Watts
750
750
750
750
• Dimensions
See dimensional drawing
•
Gas flow pressure min./max.
- Natural gas E/LL
mbar
17.4-80
17.4-80
17.4-80
17.4-80
- Liquid gas
mbar
-
-
-
-
• Gas connection values at 15 °C/1013 mbar:
- Natural gas E - (Wo = 15.0 kWh/m
3
) NCV = 9.97 kWh/m
3
m
3
/h
6.2-29.2
7.0-33.9
7.8-38.6
8.9-43.8
- Natural gas LL - (Wo = 12.4 kWh/m
3
) NCV = 8.57 kWh/m
3
m
3
/h
7.2-34.0
8.2-39.4
9.1-44.9
10.4-51.0
-
Propane (NCV = 25.9 kWh/m
3
)
m
3
/h
-
-
-
-
• Operating voltage
V / Hz
1x230/50
1x230/50
1x230/50
1x230/50
• Electrical power consumption min./max.
Watts
42/260
44/292
53/560
63/580
• Standby
Watts
5
8
5
8
• Type of protection
IP
20
20
20
20
• Permitted ambient temperature during operation
°C
5-40
5-40
5-40
5-40
• Sound power level
- Heating noise (EN 15036 part 1) (room air dependent)
dB(A)
-
69
-
76
- Flue gas noise radiated from the mouth
(DIN 45635 part 47) (room air dependent/independent of room air)
dB(A)
-
-
-
-
- Sound pressure level heating noise (depending on installation conditions)
6)
-
59
-
66
• Condensate quantity (natural gas) at 50/30 °C
l/h
26
31
35
40
• pH value of the condensate (approx.)
4.2
4.2
4.2
4.2
• Construction
B23P, C53, C63
• Flue gas system
- Temperature class
T120
T120
T120
T120
-
Flue gas mass flow at nominal heat input (dry)
kg/h
460
538
608
695
-
Flue gas mass flow at lowest heat input (dry)
kg/h
98
112
123
142
- Flue gas temperature at nominal output and operation 80/60 °C
°C
68
66
67
69
- Flue gas temperature at nominal output and operation 50/30 °C
°C
47
46
48
48
- Flue gas temperature at lowest heat output and operation 50/30 °C
°C
28
28
29
29
-
Max. permissible temperature of the combustion air
°C
48
48
48
48
- Flow rate combustion air
Nm
3
/h
376
440
497
569
-
Maximum supply pressure for supply air and flue gas line
Pa
130
130
130
130
-
Maximum draught/negative pressure at flue gas outlet
Pa
-50
-50
-50
-50
1)
Data related to NCV. The boiler series is tested for EE/H setting. With a factory setting to a Wobbe value
of 15.0 kWh/m
3
, operation in the Wobbe value range from 12.0 to 15.7 kWh/m
3
is possible without resetting.
2)
Data related to NCV
3)
Conversion acc. to EN 15502-1, Appendix J
4)
Data related to 3 % of O
2
5)
Values at determination of technical data during approval
6)
Compare notice for engineering