28
4 220 456 / 02
TECHNICAl INFORMATION
3.4.1 Overall unit dimensions
Boiler without cladding and insulation
(Dimensions in mm)
!
WARNING
The boiler must only be suspended using the four points marked as the crane suspension option in Fig. 02.
The hooks on the rear of the boiler must
not
be used to suspend it.
Fig. 32
UltraGas
®
2
Dimensions for installation as individual parts
Type
A
B
C
D
E
F
G
H
I
J
(125,150)
1765
580
880
1519
1625 1421
946
140
580
242
(190,230)
1818
680
980
1583 1678 1484 1037
140
680
236
(300,350)
1882
790
1330
1649
1742 1556
1391
140
950
316
(400,450)
1956
790
1330
1649
1816 1556
1391
140
950
316
(530-700)
2099
970
1420 1708
1940
1605 1423
159
970
316
(800-1100)
2120 1150 1606
1729 1945
1625 1722
175
1150
408
(1300,1550) 2255 1410
1916 1779
2056 1671 2042
199
1410
458
Required minimum width of door and corridor for boiler installation
The following values are the calculated minimum values
B
T =
x C
K
B
K =
x C
T
B = Boiler width
C = Maximum boiler length
T = Door width
K = Corridor width
K
T
< 150
B
C
Example calculation for the required corridor width, door width T = 1000
970
UltraGas
®
2 (700)
K =
x 1420 =Corridor width
≥ 1377
1000