22
2. LED Lights and Audible Alarm Safeties
a) "E" Control Board
KM-320MAH-E and KM-650MAH-E Auxiliary Code U-0 and Earlier
KM-515MAH-E Auxiliary Code U-1 and Earlier
At startup, a 5-second delay occurs while the control board conducts an internal timer
check. A beep occurs when power is turned off. The red LED indicates proper control
voltage and remains on unless a control voltage problem occurs. The green LEDs
1 through 4 energize and sequence from initial startup as listed in the table below.
Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2.
For details, see "II.B.1.a) "E" Control Board."
Sequence Step
LED
Energized
Components
Time LEDs are On
Min.
Max.
Avg.
1-Minute Fill Cycle 4
WV
1 minute
Harvest Cycle
1, 4, 2
Comp, FMR, HGV, WV
2 minutes
20 minutes 3 to 5 minutes
Freeze Cycle
1
Comp, FM/FMR, PM
LLV (KM-515MAH-E)
5 minutes
freeze timer
setting
30 to 35 minutes
Pump-Out Cycle
1, 4*, 3, 2
Comp, FMR, HGV, PM,
WV*
10 seconds 20 seconds *pump-out timer
setting
The built in safeties shut down the icemaker and have alarms as listed below.
No. of Beeps
(every 3 sec.)
Type of Alarm
Notes
1
High Evaporator Temp.
(temperature > 127°F)
(53°C)
Check for harvest problem (stuck HGV or relay), hot
water entering icemaker, or shorted thermistor.
2
Harvest Backup Timer
(harvest > 20 min. for two cycles
in a row)
Orange LED marked H TIMER lights up. Check for open
thermistor, HGV not opening, TXV or LLV leaking by, low
charge, or inefficient Comp.
3
Freeze Timer
(freeze > specified setting for
two cycles in a row)
Yellow LED marked F TIMER lights up. Check for F/S
stuck closed (up), WV leaking by, HGV leaking by, PM
not pumping, TXV not feeding properly, LLV not opening,
low charge, or inefficient Comp.
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6
Low Voltage
(92Vac±5% or less)
Red LED will turn off if voltage protection operates.
The control voltage safeties automatically reset when
voltage is corrected.
7
High Voltage
(147Vac±5% or more)
Legend:
Comp
–compressor;
FM
–fan motor;
FMR
–fan motor remote;
F/S
–float switch;
HGV
–hot gas valve;
LLV
–liquid line valve (KM-515MAH-E);
PM
–pump motor;
TXV
–thermostatic expansion valve;
WV
–inlet water valve