34
UDC 3300 Controller Product Manual
4/00
2.6 Control and Alarm Relay Contact Information
Control relays
Table 2-7 lists the Control Relay contact information.
ATTENTION Control relays operate in the standard control mode;
i.e., energized when output state is on.
Table 2-7
Control Relay Contact Information
Unit Power
Control Relay
Wiring
Control Relay
Contact
#1 or #2 Output
Indicator Status
N.O.
Open
Off
N.C.
Closed
Off
N.O.
Open
Closed
Off
On
On
N.C.
Closed
Open
Off
On
Alarm relays
Table 2-8 lists the Alarm Relay contact information.
ATTENTION Alarm relays are designed to operate in a failsafe mode;
i.e., de-energized during alarm state. This results in alarm actuation
when power is OFF or when initially applied, until the unit completes self
diagnostics. If the unit loses power, the alarms will function.
Table 2-8
Alarm Relay Contact Information
Variable NOT
in Alarm State
Variable
in Alarm State
Unit
Power
Alarm
Relay
Wiring
Relay
Contact
Indicators
Relay
Contact
Indicators
N.O.
Open
Open
Off
N.C.
Closed
Off
Closed
Off
N.O.
Closed
Open
On
N.C.
Open
Off
Closed
On
Содержание UDC3300
Страница 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Страница 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Страница 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Страница 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Страница 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Страница 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Страница 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Страница 293: ......