4/00
UDC 3300 Controller Product Manual
203
Diagram
Figure 5-6 is a diagram illustrating the application of the UDC 3300 for
carbon potential control.
Figure 5-6
Carbon Potential Control
T/C
f(x)
f(x)
PID
E/P
CV
Carbon
Probe
O
2
Sensor
Carburizing
Furnace
%
Carbon
PV
%
Carbon
Calc.
Output
Enrichment Gas
• SP
• 2SP
• 3SP or
RSP
Input 2
Input 1
UDC 3300
24185
millivolts
CP
Input 3—
Optional Online
CO Compensation
ATTENTION
• For Carbon control, set Input Algorithm 1 to the proper carbon sensor
used and set the PV source to IN AL 1. Input 1 will automatically
become CARBON.
• For % Oxygen control, set Input Algorithm 1 to OXYGEN. Input 1 will
automatically become OXYGEN.
• For Dewpoint control, set Input Algorithm 1 or Input Algorithm 2 to
DEW PT. Input 1 will automatically become CARBON. The
availability of Dewpoint on Input Algorithm 2 provides the capability
of controlling Carbon Potential on Loop 1 and also reading the
Dewpoint value from the same probe.
• CO Compensation—Receives external CO transmitter signal via Input
3 to provide online compensation fo the carbon calculation. Requires
that the Input 2 temperature signal be a transmitter type input.
Содержание UDC3300
Страница 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Страница 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Страница 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Страница 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Страница 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Страница 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Страница 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Страница 293: ......