4/00
UDC 3300 Controller Product Manual
179
Select tuning
parameters for each
group
The procedure in Table 5-27 shows you how select the Tuning
Parameters.
Table 5-27
Procedure for Selecting Tuning Parameters
Step
Operation
Press
Action
1
Select Tuning
Set Up Group
SET UP
until you see:
TUNING
Lower Display
SET UP
Upper Display
TUNING 2
Lower Display
SET UP
Upper Display
for Loop 1
for Loop 2
or
PID sets 1 and 2 (TUNING) are for Loop 1
and single loop applications.
PID sets 3 and 4 (TUNING 2) are for Loop 2
in two-loop and cascade control applications.
2
Select Tuning
constants
FUNCTION
LOOP 1/2
to successively display the following
constants:
Lower Display
Upper Display
TUNING CONSTANTS for
Primary Loop
PROP BAND or GAIN
RATE (MIN)
RESET (MIN OR RPM)
CYCLE
PROP BAND2 or GAIN2
RATE2 (MIN)
RESET2 (MIN OR RPM)
CYCLE2
The Tuning Constant Value
TUNING CONSTANTS for
LOOP 2
PROP BAND3 or GAIN3
RATE3 (MIN)
RESET3 (MIN OR RPM)
CYCLE3
PROP BAND4 or GAIN4
RATE4 (MIN)
RESET4 (MIN OR RPM)
CYCLE4
OR
Refer to Section 3 - Configuration for
detailed information.
You can Autotune both sets on either loop.
Refer to Section 5.21.
Use the FUNCTION key to switch
between loops.
or
To change the values.
Содержание UDC3300
Страница 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Страница 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Страница 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Страница 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Страница 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Страница 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Страница 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Страница 293: ......