260
UDC 3300 Controller Product Manual
4/00
Procedure #8
Table 9-15 explains how to troubleshoot a Communications failure.
Table 9-15
Troubleshooting a Communications Failure
Step
What to do
How to do it
1
Check the field wiring and
termination resistor.
Depending on the protocol used, refer
to the proper communications manual
installation section.
2
Make sure the Communications
Printed Wiring Board is installed
properly in the controller.
Withdraw the chassis from the case
and inspect the board. See the
exploded view (Figure 10-1) for
location of the board. Return the
chassis to the case.
3
Determine if the Communications
board is faulty by running a LOCAL
LOOPBACK TEST.
If the test fails, replace the board.
Run the Local Loopback Test.
Press [SET UP] until you see:
COM
Lower Display
SET UP
Upper Display
Press [FUNCTION] until you see:
LOOPBACK
Lower Display
DISABL
Upper Display
Press
▲
or
▼
, you will see:
LOOPBACK
Lower Display
ENABLE
Upper Display
The test will run until the operator
disables it here.
Содержание UDC3300
Страница 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Страница 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Страница 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Страница 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Страница 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Страница 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Страница 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Страница 293: ......