160
UDC 3300 Controller Product Manual
4/00
5.7 Setpoints
Introduction
You can configure the following setpoints for the UDC 3300 controller.
• A single local setpoint,
• Two local setpoints,
• One local setpoint and one remote setpoint,
• Three local setpoints,
• Two local setpoints and one remote setpoint.
To scroll through the setpoint type menu, press and hold in the
SETPOINT SELECT key. Release when the desired setpoint selection
is displayed.
ATTENTION
“KEY ERROR” will appear in the lower display if:
• You choose either local setpoint 2 or 3 or remote setpoint and your
choice has not been configured as the setpoint source.
• You attempt to change the setpoint while a setpoint ramp is enabled.
Setpoint ramp rate will apply, if enabled.
Selecting the local
setpoint source
Use the procedure in Table 5-10 to select a local setpoint source.
Table 5-10
Procedure for Selecting the Local Setpoint Source
Step
Operation
Press
Action
1
Enter Set Up
mode
LOWER
DISPLAY
until the displays read:
CONTROL
Lower Display
SET UP
Upper Display
CONTROL2
Lower Display
SET UP
Upper Display
for Loop 1
for Loop 2
or
2
Display Local
Setpoint Source
selections
FUNCTION
LOOP 1/2
until the displays read:
Lower Display
Upper Display
LSP’S
Setpoint source selections
1 ONLY
TWO
THREE
3
Select the
desired source
or
to select the desired setpoint source in the
upper display.
4
Return to control
LOWER
DISPLAY
The controller will assume normal control.
Содержание UDC3300
Страница 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Страница 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Страница 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Страница 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Страница 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Страница 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Страница 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Страница 293: ......