NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
97
Features
Intelligent Sensing Applications
C.2.3 Self-Optimizing Pre-Alarm
You can set each detector, except Heat, for Self-Optimizing Pre-Alarm (PA=1). In this Self-
Optimizing mode, the software measures the normal peak analog readings and sets the Pre-Alarm
level just above these normal peaks. This allows extremely sensitive Pre-Alarm capability with
reasonable protection against non-fire signals. The figure below shows a graphical representation
of the Self-Optimizing Pre-Alarm level:
Figure C.3 Self-optimizing Pre-Alarm Level
For more information on setting Pre-Alarm levels, refer to “Changing Detector Sensitivity” on
page 54
C.2.4 Detector Sensitivity
The control panel provides nine Sensitivity Levels for alarm detection and pre-alarm as follows:
•
Alarm Sensitivity Levels
- Select the sensitivity of a detector from 1-9 (1=highest
sensitivity; 9=lowest sensitivity).
• P
re-Alarm Sensitivity Levels
- Select one of nine levels from 1 to 9 (0=no Pre-Alarm,
1=self-optimizing, 2=highest sensitivity, 9=lowest sensitivity). You can set Pre-Alarm
operation to Action (latching) or Alert (non-latching) and to activate Special Zones. For
instructions on programming, refer to “How to Select a Pre-Alarm Level” on page 100.
Set the sensitivity levels as fixed or programmed for day and night operation. For details, refer to
“Time Control Zones” on page 93.
Awacs4
a.
w
m
f
Time (days)
Prealarm Threshold
Analog
Reading
NOTE:
For a list of all detector sensitivity levels, see Table C.2 on page 101.