NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
87
How to Program a Releasing Zone
Releasing Applications
REL
AUDIBLE
Type Code
The following contains information needed to program a Release Audible circuit for an output
circuit (control module or NAC)
.
Description
An output circuit programmed to activate an audio or visual device when all releasing outputs,
programmed to the same Releasing Zone, turn on. You can also program multiple outputs with the
REL AUDIBLE
Type Code to the same Releasing Zone. When the Releasing Zone activates, all
outputs with the
REL AUDIBLE
Type Code activate at the same time.
Programming
1. Select a control module or NAC (refer to “Modify or Delete a Point (2=point)” on page 19) to
use as a Releasing Circuit.
2. Select the
REL
AUDIBLE
Type Code, as shown in the following example (control module
shown).
3. Select the Releasing Zone (R0-R9) for your releasing application.
4. Press the
ENTER
key to save, then press the
ESC
key two times to return to the Program Change
screen.
NOTE:
An output with a
REL AUDIBLE
Type Code requires the following selections: A Releasing
Zone selection (R0-R9); An output circuit mapped to the same Releasing Zone; Switch Inhibit
selected.
Type Code selection:
REL
AUDIBLE
P R O G R M R E L A U D I B L E
M O D U L E A D D R 2 M 1 0 8
R 5 _ _ _ _ _ _ _ _
I * *
2 M 1 0 8
Releasing Zone
selection (R5 shown)
Walk Test
Selection: * = off
Silenceable: * = off
Switch Inhibit: I = selected