NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
21
Basic Program
Programming
Extended
Label
12 character custom label
extension.
See “Custom Label” above.
Note that spaces must be input by the user, including any space necessary
between the custom and extended label fields. An 80-column printout will
run the two fields together.
CBE List
Five zones can be listed - one
zone, Z03, is shown in the
example. Up to 4 more could
be added to this detector.
Zones can be changed or added to the CBE list by placing the cursor in the
zone field using arrow keys, then typing.
Defaults:
Alarm
Sensitivity
The alarm sensitivity level,
with 9 the least sensitive
alarm level and 1 the most
sensitive alarm level.
Refer to Table C.2 on page 101 for settings. Select by placing the cursor in
the field using the arrow keys, then either pressing the
NEXT
or
PREVIOUS
keys to make the selection, or typing the value.
Defaults:
Pre-alarm
level
Shows the Pre-Alarm level
setting—a number between 0
and 9—as follows:
0 – no Pre-Alarm
1 – self optimizing
2 – most sensitive Pre-Alarm
level
9 – least sensitive Pre-Alarm
level
Refer to Table C.2 on page 101 for settings. Select by placing the cursor in
the field using the arrow keys, then either pressing the
NEXT
or
PREVIOUS
keys to make the selection, or typing the value.
Defaults:
Cooperative
Multi-
detector
mode
Indicates the cooperative
multi-detector mode (A in the
example).
Select by placing the cursor in the field using the arrow keys, then either
pressing the
NEXT
or
PREVIOUS
keys to make the selection, or typing the
value.
*
= OFF (Default)
A
combines the detector's alarm decision with the next address above
B
combines the detector's alarm decision with the next address below
C
combines the detector's alarm decision with the next address above and
the next address below
Alarm
verification
Indicates the alarm
verification setting (V in the
example).
Indicates Alarm Verification (V=on, *=off). Select by placing the cursor in the
field using the arrow keys, then pressing the
NEXT
or
PREVIOUS
keys to make
the selection. Refer to “Interpreting a Detector Status Display or
Maintenance Report” on page 104 for more information on the alarm
verification feature.
Note: Do not use this setting when an alarm activation requires activation of
two or more automatic detection devices.
Table 2.2 Detector Program Values
Field
Description
Set as Follows
Zone 01 (Heat detectors)
Zone 02 (Ion detectors)
Zone 03 (Photo detectors, Beam detectors)
Zone 04 (Laser detectors)
Zone 05 (Multisensor)
A8 (Photo)
A6 (Ion)
A6 (Laser)
A5 (Multisensor)
P8 (Photo)
P6 (Ion)
P6 (Laser)
P5 (Multisensor)