NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
63
How to Program a Releasing Zone
Releasing Applications
When an initiating device activates, you must press and hold the Abort Switch or the control panel
will send the command to dump releasing agents when the Delay time (15 seconds shown) expires.
The Abort selection (ULI, IRI, NYC, or AHJ) determines the function of the Abort Switch.
Figure A.3 Example of a Basic Configuration for an Abort Switch
SYSTEM
NORMAL
SYSTEM
ACTIVATED
Type Code
RELEASE
CKT
Type Code
REL
CKT
ULC
Type Code
REL
AUDIBLE
Type Code
REL
END
BELL
Releasing Zone R05 sample programming selections
Example: If you program B01-B03 as shown,
these outputs activate at release.
Example: If you
program B04 as
shown, this output
activates when the
release is finished.
R05
Monitor
Module with
ABORT
SWITCH
Type Code
Detector
Detector
Abort station with Abort Switch
and Manual Release lever
B01
B02
B03
B04
P R G R E L E A S E F U N C T
R E L E A S E C O N T R O L
D E L A Y = 1 5 A B O R T = U L I C R O S S = N S O K = 0 0 0 0 R 0 5