NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
71
How to Program a Releasing Zone
Releasing Applications
Figure A.9 Illustrated Example of Cross Zone Programming
A listing of each Cross Zone option and the conditions required to activate the Releasing Zone,
according to the example shown above.
Select a time for the Releasing Zone Delay Timer (refer to“Programming a Delay Timer” on page
61.)
Cross Zone
Selection (Cross=)
Condition(s) Required to Activate the Releasing zone
Cross=
N
An alarm from any detector or module activates the releasing circuit.
Cross=
Y
An alarm from any two detectors or modules activates the releasing
circuit.
Cross=
Z
An alarm from two detectors or modules mapped to different Software
Zones, but mapped to the same Releasing Zone.
• An alarm from 2D101 and 2D103
• An alarm from 2D102 and 2D104
• An alarm from 2D101 and 2D104
• An alarm from 2D102 and 2D103
The two detectors listed in each set above are each mapped to different
zones, but both list ZR1 in their CBE.
Cross=
H
Activation of heat detector 2D104 and one smoke detector (2D101,
21D102, or 2D103) or a module mapped to the same releasing zone.
To Program
Do this
Cross Zones
Type N, Y, Z, or H in the CROSS= field, or press the
NEXT
or
PREVIOUS
keys,
or
, until N, Y, Z or H appears in the that field.
Releasing
Zone ZR1
Software
Zone Z02
Software
Zone Z01
Smoke
Detector
2D102
Heat
Detector
2D104
Smoke
Detector
2D103
Smoke
Detector
2D101
REL
B03
CBE list = Z02 ZR1
CBE list = Z01 ZR1
CBE list = Z01 ZR1
CBE list = ZR1