42
NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
Programming
Basic Program
ACS Selection Group P (SLC #1, Modules 65-100 and Detectors 1-14):
Table 2.27 ACS Group P (see note 3)
Point
Type
Red LED
Yellow LED
Switch Function*
1
Input
SLC 1, Module 65 Alarm
SLC 1, Module 65 Trouble Not Used
2
Input
SLC 1, Module 66 Alarm
SLC 1, Module 66 Trouble Not Used
3
Input
SLC 1, Module 67 Alarm
SLC 1, Module 67 Trouble Not Used
to
to (see note 1)
to (see note 1)
36
Input
SLC 1, Module 100 Alarm
SLC 1, Module 100
Trouble
Not Used
37
Input
SLC 1, Detector 1 Alarm
SLC 1, Detector 1 Trouble Not Used
38
Input
SLC 1, Detector 1 Trouble
Maintenance Urgent
SLC 1, Detector 1 Trouble
Maintenance Alert
Not Used
39
Input
SLC 1, Detector 2 Alarm
SLC 1, Detector 2 Trouble Not Used
40
Input
SLC 1, Detector 2 Trouble
Maintenance Urgent
SLC 1, Detector 2 Trouble
Maintenance Alert
Not Used
to (see note 2)
to (see note 2)
63
Input
SLC 1, Detector 14 Alarm
SLC 1, Detector 14
Trouble
Not Used
64
Input
SLC 1, Detector 14
Trouble Maintenance
Urgent
SLC 1, Detector 14
Trouble Maintenance Alert
Not Used
* Pressing the switch button when the Switch Function is “Not Used” will cause the associated LED to stop
blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.
NOTE:
1. Point number to Module number relationship is sequential. To determine Point to Module
relationship add 64 to Point number to arrive at Module number.
2. Point number to Detector number relationship is sequential in groups of 2. Since each detector
occupies 2 points, to determine the Point to Detector relationship, count by 2 starting from point
37.
3. This group is only available when UDACT setting is programmed as option 2 and will
automatically be assigned to ACS address 24.