116
NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
Type Codes
Type Codes for Output Devices
F.5.3 NAC Type Codes
A comprehensive list of Type Codes for panel NACs. For instructions on programming Type
Codes, refer to “Modify or Delete a Point (2=point)” on page 19.
GEN SUPERVIS
N
NAC
Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under any
Supervisory condition (includes sprinkler type). It is programmed as “switch inhibit”.
GEN TROUBLE
N
NAC
Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under any
System Trouble condition. It is programmed as “switch inhibit”.
GENERAL PEND
N
NAC
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will activate upon
receipt of an alarm and/or trouble condition, and remain in the ON state until all events
have been ACKNOWLEDGED.
TROUBLE PEND
N
NAC
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will activate upon
receipt of a trouble condition, and remain in the ON state until all troubles have been
ACKNOWLEDGED. It is programmed as “switch inhibit”.
MNS GENERAL
N
NAC
Mass notification supervised output.
MNS CONTROL
1
N
NAC
Mass notification supervised NAC.
MNS STROBE
1
N
NAC
Mass notification supervised NAC.
MNS SPEAKER
1
N
NAC
Mass notification supervised NAC for speaker circuits.
MNS RELAY
1
N
NAC
Mass notification relay output.
*
The FCM-1-REL checks for shorts with all releasing type codes.
1
The type code is not compatible with FirstCommand applications.
Table F.3 Control Module Type Codes (2 of 2)
Table F.4 NAC Type Codes
Type Code
Silenceable
(Y/N)
Device Function
CONTROL
Y
Supervised NAC
BELL CIRCUIT
Y
Supervised NAC for notification appliance
STROBE CKT
Y
Supervised NAC for notification appliance
HORN CIRCUIT
Y
Supervised NAC for notification appliance
AUDIBLE CKT
Y
Supervised NAC for notification appliance
SPEAKER
N
Supervised NAC for speaker circuits
REL END BELL
N
Supervised NAC
blank label
Y
Supervised NAC for undefined device
REL CKT ULC
N
Releasing Circuit, power-limited, supervised for opens, shorts and
ground faults (always non-silenceable)
RELEASE CKT
N
Releasing circuit, nonpowerlimited, supervised for opens and
ground faults
REL AUDIBLE
Y
NAC, activated upon release
REL CODE
BELL
Y
Supervised NAC (NFS2-640 NAC only)
INSTANT RELE
N
NAC, short = normal; supervised for open circuits and ground
faults. Always non-silenceable and switch-inhibited.
ALARMS PEND
N
Output that will activate upon receipt of an alarm condition, and
remain in the alarm state until all alarms have been acknowledged.
It is programmed as “switch inhibit”.
CONTROL NAC
Y
Supervised NAC
GEN ALARM
N
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode)
configured as a Municipal Box Transmitter for NFPA 72-2002
Auxiliary Fire Alarm Systems applications (MBT-1 required). This
Type ID can also be used for general alarm activation. It is
programmed as “switch inhibit”.
GEN SUPERVIS
N
Control Module, an XPR-8 relay, or an XP5-C (in relay mode)
activated under any Supervisory condition (includes sprinkler type).
It is programmed as “switch inhibit”.
GEN TROUBLE
N
Control Module, an XPR-8 relay, or an XP5-C (in relay mode)
activated under any System Trouble condition. It is programmed as
“switch inhibit”.