74
NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
Releasing Applications
How to Program a Releasing Zone
ABORT
SWITCH
Type Code
The following contains information needed to program an Abort Switch for a monitor module
Description
A monitor module, connected to a UL-listed abort station (such as the Notifier NBG-12LRA), that
you use as an abort switch for a Releasing Zone. You can program multiple monitor modules with
the
ABORT
SWITCH
Type Code that work like multiple conventional abort switches on a
conventional zone.
Programming
1. Select a monitor module to use as an Abort Switch (refer to “Modify or Delete a Point
2. Select the
ABORT
SWITCH
Type Code.
3. Select the Releasing Zone (R0-R9) for your releasing application.
4. Press the enter key to save, then press the esc key until you return to the Program Change
screen.
5. Select the type of Abort Switch for your releasing application (refer to “Abort Switches” on
page 62).
Example
A programming example of a monitor module programmed as an Abort Switch for Releasing Zone
R5.
Figure A.10 Monitor Module Configured as an Abort Switch
Releasing Zone selection (R1 shown)
Type Code selection:
ABORT
SWITCH
P R O G R M A B O R T _ S W I T C H M O D U L E A D D R 2 M 1 0 1
R 1 _ _ _ _ _ _ _ _
2 M 1 0 1
SYSTEM
NORMAL
SYSTEM
ACTIVATED
Detector
Control
Module
R05
NBG-12LRA
station with
Abort Switch
B01
Monitor
Module
Type Code
ABORT
SWITCH
NBG1
2L
R
A
face
.wm
f