ID61/62 Series Panel - Operating Manua
l
Automatic
Alarms - What to do
10
997-458-000-8, Issue 8
January 2010
2
If a service contact number has been entered during
panel commissioning, the LCD alternates between
the fault message(s) and the following:
Note:
Press the MUTE BUZZER pushbutton to silence
the panel’s internal buzzer.
3
When the cause of the fault has been cleared, press
the RESET pushbutton.
3.3.1 Power Fail
The loss of a power supply causes the panel to enter a
Power Fail condition. This condition is confirmed by the
illumination of the POWER SUPPLY FAULT LED, general
FAULT LED and the operation of the internal buzzer. The
LCD displays:
a. Fault indication
b. Fault number currently displayed
c. Total number of faults logged
d. Time fault was logged
e. A text message describing the fault.
A battery fault is shown on the LCD as follows:
2 If a service contact number has been configured, the
LCD alternates between the power fault message and
the service contact number.
Note:
Press the MUTE BUZZER pushbutton to silence
the panel’s internal buzzer.
3
When the cause of the fault has been cleared, press
the RESET pushbutton.
Status: NORMAL
Sat 05/01/2002
00:00:00
If both the AC and
Battery power fail, the
indicators and LCD are
non-operational.
FAULT
01 / 02
14:55
BATTERIES MISSING
FAULT
01 / 03
14:55
For Service Contact ***** ******
A
D
B
C
E
Status: NORMAL
Sat 05/01/2002
00:00:00
FAULT
01 / 02
14:55
NO MAINS SUPPLY
A
D
B
C
E
DISABLEMENT
FAULT
TEST
POWER SUPPLY FAULT
EARTH FAULT
POWER
PLANT ALARM
FIRE OUTPUT ACTIVE
DELAYS ACTIVE
FIRE OUTPUT: FAULT / DISABLED
FIRE CONTROL O/P: FAULT / DISABLED
PRE- ALARM
SYSTEM FAULT
SOUNDER: FAULT / DISABLED