ID61/62 Series Panel - Operating Manual
Operator
Actions at Panel
25
997-458-000-8, Issue 8
January 2010
4.9.5 Outputs - User Option
The Test Outputs option, accessed from the Test Menu,
tests the panel’s internal sounder and relay circuits and
the Signalling Line Circuit (SLC) loop outputs. To perform
this test:
Test Internal Outputs
1
From the Test Menu, press the ‘
5
’ button on the
numeric keypad to select the Outputs option.
2
The LCD displays the Outputs menu. Press the ‘
1
’
button on the numeric keypad to display the Internal
Test menu.
3
Use the ‘
2
/
8
’ buttons to select the internal output
required for testing and press the ‘
5
’ button to start
the test. The LCD then displays the following:
4
Check that the output operates. To stop the test, press
the ‘
4
’ button. Press the ‘
4
’ button again to return
to the Test Outputs menu.
Test SLC Outputs
1
From the Outputs menu, press the ‘
2
’ button on the
numeric keypad to display the SLC Output Test menu:
2
Use the ‘
2
/
8
’ buttons to select the output required
for testing and press the ‘
5
’ button to start the test.
The LCD then displays the following:
3
Check that the output operates. To stop the test, press
the ‘
4
’ button. Press the ‘
4
’ button again to return
to the Test Outputs menu.
[U0 Test]
1:LEDs
2:LCD
3:Zones
4:Auto High Test
5:Outputs
¦
: More
[Internal Test]
B:01
SDR
: Start
¦
: Change Output
<:Exit
[U0 Outputs]
1:Internal
2:SLC
3:Loop Power
[Internal Test]
B:01
SDR
Output test in progress
<:Stop
[U0 Outputs]
1:Internal
2:SLC
3:Loop Power
[SLC Test]
M:01
SDR
: Start
¦
: Change Output
<:Exit
[SLC Test]
M:01
SDR
Output test in progress
<:Stop
5
2
8
or
5
5
2
8
or
2
1