ID61/62 Series Panel - Operating Manual
Operator
Actions at Panel
15
997-458-000-8, Issue 8
January 2010
4.4 END DELAY / EVACUATE Pushbutton
The END DELAY/EVACUATE pushbutton is used to
initiate the Evacuate procedure. If this pushbutton is
operated while a delay is active, all delays are cancelled
and all sounders designated in the pre-configured
Evacuate rule are activated.
Fire Alarm Condition
Providing the pushbuttons have been enabled for Level
1 operation and delays are active the following occurs:
1
Press the END DELAY/EVACUATE pushbutton. The
following is typically displayed:
2
No further action is needed until it is required to silence
the sounders, in which case the SILENCE/RESOUND
pushbutton should be pressed, see
Section 4.5,
Silence / Resound pushbutton
.
Note:
If the pushbuttons are enabled to operate at
Level 2, enter the Level 2 passcode in the manner
described in the RESET pushbutton procedure
(
Section 4.6
).
No Alarm Condition
In quiescent mode, pressing the END DELAY/EVACUATE
pushbutton immediately sounds the internal buzzer,
operates all outputs configured in accordance with the
CBE rules (configured at time system was commissioned)
and the LCD displays the ‘EVACUATE’ message.
OPERATOR
01 / 05
14:55
EVACUATE
OPERATOR 01 / 01
14:55
EVACUATE