ID61/62 Series Panel - Operating Manual
Operator
Actions at Panel
32
997-458-000-8, Issue 8
January 2010
4.10.3 Day Mode - User Option
If Day Mode is enabled during panel commissioning, this
option allows the user to activate/deactivate Day Mode
delays during the set Day Mode time period. This has no
effect on any sensor sensitivity changes that may have
been configured during commissioning. Any sensor
sensitivity changes will automatically occur at the set Day
Mode period start and end times.
To Disable/Enable Day Mode, proceed as follows:
1
From the Disable / Enable menu, press the ‘
3
’ button
to display the following:
2
Press the ‘
5
’ button to confirm the requested
operation. The LCD automatically returns to the
Disable/Enable menu.
If Delays have been configured the DELAY ACTIVE
LED illuminates when Day Mode is started.
3
To end Day Mode, repeat steps 1 and 2 (the display is
as shown below):
The DELAY ACTIVE LED will extinguish when the Day
Mode operation has been ended, either when day
mode is turned off or when the timer has timed out.
No delays are active.
Note:
If Day Mode is NOT cancelled manually, Day Mode
delays are automatically deactivated at the end of
the set time period.
[U0 Disable/Enable]
1:Zone
2:Outputs
3:Day Mode
4:Delays
Start Day Mode
Press
to confirm
<:Cancel
[U0 Disable/Enable]
1:Zone
2:Outputs
3:Day Mode
4:Delays
End Day Mode
Press
to confirm
<:Cancel
3
5
DELAYS ACTIVE
FIRE OUTPUT ACTIVE
FIRE OUTPUT: FAULT / DISABLED
POWER
PLANT ALARM
FIRE
TEST
DISABLEMENT
[U0 Disable/Enable]
1:Zone
2:Outputs
3:Day Mode
4:Delays
5
The FIRE CONTROL O/P: FAULT/DISABLED, FIRE
OUTPUT: FAULT/DISABLED and the SOUNDERS
DISABLED LEDs extinguish when the corresponding
outputs have been enabled. The DISABLEMENT LED
will only extinguish when ALL disablements have been
enabled.