ID61/62 Series Panel - Operating Manual
Operator
Actions at Panel
17
997-458-000-8, Issue 8
January 2010
CONTROL KEY LOCKED - ACCESS REQUIRED
Enter Level 2/3 Passcode: . . . .
< : BackSp
CONTROL KEY LOCKED - ACCESS REQUIRED
Enter Level 2/3 Passcode: * * * *
< : BackSp
5
4.6 RESET Pushbutton
The RESET pushbutton is used to clear all non-quiescent
conditions and return the panel to a normal quiescent
condition. Provided that the control keys have been
enabled for Level 1 operation, the following occurs:
a. All FIRE and FAULT lamps are switched off.
b. All sounders cease to operate.
c. The system status returns to NORMAL, provided that
no operator actions are being carried out.
If the pushbuttons are enabled to operate at Level 2, follow
the procedure below:
1
Press the RESET pushbutton. The LCD displays the
following:
2
Either turn the keyswitch, or enter an appropriate
Level 2 access code and confirm using the ‘
5
’ button.
If Alarm(s), and/or Fault(s) conditions are still present
when RESET is operated, the condition will be reported
as if it were a completely new event with appropriate
annunciation.