ID61/62 Series Panel - Operating Manual
Operator
Actions at Panel
26
997-458-000-8, Issue 8
January 2010
[U0 Outputs]
1:Internal
2:SLC
3:Loop Power
COMMISSION MODE ACCESS
Enter Level 3 passcode -
< BackSp
To perform a Loop Booster
output test an access level 3
passcode is required.
[LBM Test]
Loop : Both Sides
0%
: Start
¦
: Change<:Exit
Test Loop Booster Outputs
A number of tests are available to satisfactorily test the
operation of the Loop Booster Modules (LBMs) during
alarm conditions. The tests are designed so that the power
delivered to the loop by the panel can be switched off from
either end, or each LBM in turn can be prevented from
being turned on. The tests are designed, when combined
with a walk-test, to check that:
a. The panel operates all loop-powered devices correctly
with the LBM(s) with
one
source of loop power isolated.
b. All loop-powered outputs operate correctly with any individual
LBM disabled or with the loop only powered from one end.
1
Press the ‘
3
’ button on the numeric keypad to select
the Loop Booster test procedure. With the panel currently
at access level 2, the following warning is displayed
prompting for entry of access level 3 passcode:
2
Having entered the access level 3 passcode, press
the ‘
5
’ button to start the test.
3
Before the test starts a 0% percentage indication of the
equipment under test is displayed on the top line. As the test
progresses, the percentage value increases to 100% to
indicate that all loop-powered devices under test are operating
correctly. This percentage value may go down if a device
starts reporting incorrectly or becomes de-activated.
4
Press the ‘
2
/
8
’ pushbuttons to select the other Loop
Booster options: ‘In Only’ or ‘Out Only’
5
To perform a loop test without loop booster support
you can turn off individual LBMs while testing that loop-
powered sounders are still able to operate correctly.
6
Press the
4
’ button to cancel the test and return to
the Test Menu.
Note:
If the test is not cancelled manually, it is cancelled
automatically 4 hours after the last panel keystroke.
[LBM Test]
Loop : Both Sides
0%
: Start
¦
: Change<:Exit
[LBM Test]
Loop : Out Only
0%
: Start
¦
: Change<:Exit
[LBM Test]
Loop : In Only
0%
: Start
¦
: Change<:Exit
[LBM Test]
M nn : Inactive
0%
: Start
¦
: Change<:Exit
Select ‘Both Sides’ to test loop-
powered sounders only (LBMs
are not turned on).
Select ‘In Only’ to perform test
with loop powered only from the
‘Loop Out’ end.
Select ‘Out Only’ to perform
test with loop powered only from
the ‘Loop In’ end.