PAGE - 2
INSTALLATION MANUAL
AM-8200
NOTIFIER ITALIA
Doc. M-162.2-AM8200-ENG Rev A.2
AM8200_manu-inst
Nazional Rules Compliants
EN 54 : Information
EN54
This fire detection control unit is in accordance with the requirements of
EN54-2 and EN 54.4 rules.
In addition to the basic EN 54 requirements, the control unit is in conformity with the
following optional operation requirements
Optional Functions
EN 54.2 reference
Output to fire alarm devices
Output to fire protection equipment
Fault monitoring of fire protection equipment
Delays to outputs
Dependencies on more than one alarm signal
Fault signals from point
Total loss of power supply
Disablement of addressable points
Test Condition
Indication of the test condition
Indication of zones in the test state
7.8
7.10
7.10
7.11
7.12 ( type A )
8.3
8.4
9.5
10
10.2
10.3
EN54
The power supply section of the AM-8200 control unit is in conformity with the
following EN54-4 requirements.
Function
EN 54.4 reference
Power supply from main source
Power supply from battery source in standby
Re-charging and check of the battery source
Power supply fault detection and signalling
5.1
5.2
5.3
5.4
This device must be installed and must operate in accordance with these instructions and
to the rules in force in the installation place.
This product must be disposed of using the appropriate bins for electrical and electronic products.
This product must not be placed in bins for collection of other waste types.
EN54
!
EN54-2 13.7
Max 512
Sensors / Manual
Call Points per
microprocessor.
AM-8200 control unit has a maximum capacity of 636 sensors and 700
address for modules each two loops.
If this function is not appropriately used, it can contravene the EN54.2
requirements.
This limit includes the possible conventional sensors and buttons
connected to the system with zone modules.
Therefore, check the number of installed devices and ensure they are in
conformity with the rule
.