PAGE - 18
INSTALLATION MANUAL
AM-8200
NOTIFIER ITALIA
Doc. M-162.2-AM8200-ENG Rev A.2
AM8200_manu-inst
Relay outputs
Instructions to setting the relay outputs as N.O. / N.C. or Supervised
General Fault relay
The General Fault relay is usually in
energized state. It is de-energized in Fault
condition .This output is available in free
voltage.
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads
FUNCTION
Siren
USR2
USR1
General Alarm
General Fault
CHARACTERISTICS
1 contact controlled by 24Vcc / 2A resistive
Max 2A resistive 30 Vdc, NO-NC or supervised output 0,3A Fused, selectable through Jumper JUSR2
(refer to basic board topography)
Max 2A resistive 30 Vdc, NO-NC or supervised output 0,3A Fused, selectable through Jumper JUSR1
(refer to basic board topography)
Max 2A resistive 30 Vdc, NO-NC or supervised output 0,3A Fused, selectable through Jumper JALL
(refer to basic board topography)
Max 2A resistive 30 Vdc, NO-NC or supervised output 0,3A Fused, selectable through Jumper JGST
(refer to basic board topography)
Main Fault output
i
CNU
COM NO/NC
19 20
N.O. Contact
(Default)
N.C. Contact
Supervised output
AM-82-MB Board
Setting of the general fault
output with N.O. contact
(Jumper JGST).
Setting of the general fault
output with N.O. contact
(Jumper JGST).