PAGE - 20
INSTALLATION MANUAL
AM-8200
NOTIFIER ITALIA
Doc. M-162.2-AM8200-ENG Rev A.2
AM8200_manu-inst
NOTE:
Connect the 47KΩ , ¼ W EOL
resistor only on last sounder of
the line
ATTENTION
:
Polarity
displayed
are
in
Activated condition, at idle
condition, they are inverted
USR1 and USR2 relays
The USR1 and USR2 relays are available in free voltage contacts
or
as supervised outputs.
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads
Selection of type of contact (Normally open ,
Normally closed or supervised outputs ) see page 15.
NOTE:
To program the activation of these outputs
refer to “AM-8200 Programming Manual.
USR1 Output
Supervised output (resettable fuse 0.3A) with EOL resistor 47K
Ω
Polarized devices (electronic sirens, etc.)
47 K
¼ W
14
13
Non-polarized devices (Bells, relays, etc)
47 K
¼ W
2 x 1N 4004
14
13
CNU
USR1
COM NO/NC
13 14
CNU
USR2
COM NO/NC
15 16
USR1 - USR2 Output
Setting of the USR1 output
with N.O. contact
(Jumper JALL).
Setting of the USR1 output
with N.C. contact
(Jumper JALL).
Setting of the USR1
output as supervised
output (Jumper JALL).