POWER SUPPLY – Current calculation
The power supply must be able to continuously power all the internal system devices (and all external devices)
during the stand-by period, that is in NON-alarm conditions.
-
Use the table A to calculate the load in stand-by conditions.
-
Use the table B to calculate the additional current which is necessary in Alarm conditions
A 24 Vcc internal power supply for a total of 4 Ampere is available on the power supply for the system operation
Table 1
NORMAL condition
ALARM condition
A
B
Item
Q Current each
Total
Current
(dev x Q)
Current each
Total Current (dev
x Q)
AM-8200
AM-8200 CPU(AM8200-KLCD)
179 mA
345 mA
LIB-8200
50 mA
92 mA
AM82-2S2C
28 mA
28 mA
AM82-BST-C
39 mA
39 mA
SIB-8200
62 mA
62 mA
Devices connected to Sounder Output
1
0
0
|_________|
|_________|
Loops
2
Current
Refer to
Table 3
Loop 1
|_________|
|_________|
Loop 2
|_________|
|_________|
Loop 3
|_________|
|_________|
Loop 4
|_________|
|_________|
User Output current
3
(Max 2A )
(Max 2A)
LCD-8200
Bells
0
0
|_________|
|_________|
Sounders
0
0
|_________|
|_________|
Strobes
0
0
|_________|
|_________|
Other devices
|_________|
|_________|
|_________|
|_________|
Total
4
=
Total =
(x24h) or
(x72h) =
x 0.5 h =
Stand-by (A)
Ah
Alarm (B)
Ah
Ah Battery = (A + B) x 1.2
5
=
Ah