AM-8200
Installation Manual
PAGE - 17
AM8200_manu-inst
Doc. M-162.2-AM8200-ENG Rev A.2
NOTIFIER ITALIA
DIP SWITCH SW401 on CPU Board
Dip switch
Note
1
2
3
4
OFF OFF
OFF OFF
Normal Operating setting
ON
OFF
OFF OFF
Copy the configuration in the USB memory key
OFF OFF
OFF ON
Firmware updating
ON
OFF
OFF ON
Restore factory configuration
ON
ON
ON
ON
from USB memory key loads configuration previously prepared by PK-8200 SW Tool
AM-82-MB Terminal Board
CN1
terminal
N° description
Function
Note
L
Phase
230Vac mains Power
Fused with 2 AL
Ground
N
Neutral
CNU
terminal block
N° Description
Characteristics
Note
20
Fault relay N.C./ N.O.
Max 30V 2A
Select N.O./N.C. with
JGST Jumper
or
supervised output
(resettable fuse
0.3A) with EOL resistor
47KΩ
19
Fault relay “Common”
18
Sounder (Negative in non alarm)
1 A resettable fuse (this is a
polarity inversion output).
EOL resistor = 47KΩ
17
Sounder (positive in non alarm)
16
User 2 Relay N.C./ N.O.
Max 30V 2A
Select N.O./N.C. with
JUSR2 Jumper
or
supervised output
(resettable fuse
0.3A) with EOL resistor
47KΩ
15
User 2 Relay “Common”
14
User 1 Relay N.C./ N.O.
Max 30V 2A
Select N.O./N.C. with
JUSR1 Jumper
or
supervised output
(resettable fuse
0.3A) with EOL resistor
47KΩ
13
User 1 Relay “Common”
12
Alarm Relay N.C./N.O.
Max 30V 2A
Select N.O./N.C. with
JALL Jumper
or
supervised output
(resettable fuse
0.3A) with EOL resistor
47KΩ
11
Alarm Relay “Common”
10
GND USR
2 A resettable fuse
9
+24V USR
8
Line 2 B-
Detection LINE 2
7
Line 2 B+
6
Line 2 A-
5
Line 2 A+
4
Line 1 B-
Detection LINE 1
3
Line 1 B+
2
Line 1 A-
1
Line 1 A+
JUSR2
Flat cable for interconnection with LIB-8200
User terminal block
Connector for optional board
Flat cable for interconnections
with AM8200-KLCD
Flat cable for interconnection with AM-82-BBMB
JGST
JALL