PAGE - 36
INSTALLATION MANUAL
AM-8200
NOTIFIER ITALIA
Doc. M-162.2-AM8200-ENG Rev A.2
AM8200_manu-inst
System Test and Commissioning
The Control unit installation must be performed after having carefully read the instructions contained in the
installation manual and the programming manual.
Once mechanical installation of the control unit has been completed, perform the following operations:
Check the correct detection line wiring through a multi-meter (refer to chapter Test Procedure for the
analogue system lines in this manual).
Connect the detection lines to the control unit.
Connect the main alarm siren (fitted with 47 KW ¼ W balance resistance) on the CNU-18 and 17 terminals
(refer to basic board topography )
To correctly dimension the batteries to be used, check the autonomy that the system must guarantee in case
of 230 Vac. mains breakdown.
Connect the control unit to the 230 Vca mains by means of a three-pole cables: phase, earth, neuter (the earth
cable must be longer than the phase and neuter ones) on the CN1 terminal block (the earthing connection is
compulsory) and must be fixed to the cabinet by means of a cable fixing device so that it cannot be
accidentally stripped off.
The power supply connection must be performed through the following phases
(refer to basic board topography)
:
Turn off the main switch of the 230 Vca mains which powers the control unit;
Disconnect the CN1 terminal block from the control unit
Connect the 230 Vca mains to the CN1 terminal block;
Connect the CN1 terminal block to the control unit ;
Turn on the main switch of the 230 Vac mains
Install and connect the batteries as indicated in this manual
When the control unit is powered check the following conditions on the front panel:
Green led “POWER OK” = on
Yellow led ” FAULTS”
= flashing;
Buzzer
= continuous sound
By pressing the Buzzer Silencing key, the buzzer is switched off and the “POWER UP” fault indication is displayed
By Pressing the “RESET” key the request to enter the level 2 password is displayed
(default = 22222) .
Enter the password and check the following conditions:
green led “POWER OK”
= on
yellow led “FAULTS”
= off
no faults signalling on the display
To program the control unit consult the chapter “RECOMMENDED SEQUENCE TO PERFORM THE CONTROL
UNIT PROGRAMMING” in the Operator and Programming manual.