PAGE - 12
INSTALLATION MANUAL
AM-8200
NOTIFIER ITALIA
Doc. M-162.2-AM8200-ENG Rev A.2
AM8200_manu-inst
Mains and Batteries connection
The connection to the 230 Vac power supply mains must be performed through three-conductor cable (phase- neuter-
earth).
The identification of the earth conductor coming from the mains must be performed on the CN1 terminal block (refer
to basic board topography) and must be fixed at the cabinet by means of cable –tightening strip so that it cannot be
accidentally stripped off from the terminal block.
The 230 Vac power supply cable must be fixed inside the control unit by means of an appropriate cable fixing device.
NOTE: The cable fixing collars must be HB flammability class.
The mains supply conductors shall not be consolidated by means of a soft welding..
A sectioning device external to the control unit must be provided for the 230 Vac power cable (contact separation: 3
mm min.) The sectioning device must be omni-polar or must disconnect the line phase
Power Supply connection must be done following this procedure:
(Refer to Base Board)
1 – Turn off the main power switch of the 230 Vac mains.
2 – Disconnect the CN1 terminal block from the control unit.
3 – Connect the mains cable.
4 – Re-connect the CN1 terminal block
5 – Turn on the mains switch
6 – Install and connect the batteries as indicated in this manual.
N.B.: Once the control unit has been powered, it will automatically start operating.
However, in accordance with the battery storage period, it is necessary to wait some hours before the
batteries are completely re-charged.
7 – Check the operation of the LED indicators on the panel, according to the paragraph “TEST AND STARTING
OPERATION”.
8 – Close the control unit.
NTC Probe
MAINS 230Vac
Toroid
Plastic Band
Batteries 2x12V
NTC Probe
AM-8200
AM-8200-BB
Batteries 2x12V
Adhesive tape for
probe locking
Adhesive tape for
temperature probe
locking
MAINS INPUT 230Vac (CN1)
L
N
GROUND
FUSE 2AL
In protection to
AM-8200
FUSE 2AL
In protection to
AM-8200BB